Rockwool 50mm Ablative Coated Batt
Rockwool 50mm Ablative Coated Batt is a mineral wool insulation product, pre-coated on both sides with a high performance ablative coating. It has been comprehensively tested as part of the Rockwool Firepro® range of fire protection products and can be installed across a variety of services and substrates including solid walls and floors, flexible walls, multi-service penetrations, the head of wall, blank seals and face fixed applications as well as large framed service voids.
Ablative Coated Batts are not intended for use as load-bearing seals. Where a load bearing seal is required, Rockwool Firestop Compound should be considered.
Can provide fire resistance from a single thickness batt - tests have proved the capability of a single 50mm Batt to provide up to 2 hours fire resistance integrity and insulation. Where 4 hours integrity and insulation is required, the use of the 60mm Ablative Coated Batt is recommended.
- Comprehensively tested as part of the FIREPRO suite of solutions
- Suitable for sealing wall and floor voids containing most commonly used services and substrates
- Can be used as a blank seal and a head of wall seal
- Lightweight and simple to install
- Tested for air tightness, providing an additional smoke and acoustic seal
Applications
- Multiple substrates including: solid walls and floors; flexible walls
- Multi-service penetrations
- Head of wall
- Blank seals
- Face-fixed applications
- Large-framed service voids
Accreditations
- BS EN 1366-3: 2009 and the dedicated fire resistance standard for linear joint seals
- BS EN 1366-4:2006
- Ablative Coated Batt has been classified in accordance with BS EN 13501-2
- Third party accreditation through Certifire
- CE Marked to EAD 350454-00-1104 - ETA 20/1128
Fire resistance - 50mm Ablative Coated Batt - Up To 2 Hours /60mm Ablative Coated Batt - Up To 4 Hours.
Size
1200x600x50mm - This fire batt is coated both sides
1200x600x60mm - Available on request - This fire batt is coated both sides
Data Sheet Links
Product Data Sheet
50mm Installation Guide
Safety Data Sheet
Technical Datasheet
The above information is based on current test data, health and safety information and application instructions supplied by the manufacturer of the products. It is supplied for guidance and to the best of our knowledge is true and accurate. Customers should satisfy themselves to the suitability of the products in its intended use and no guarantee is given or implied as the conditions of actual use are beyond our control. If in doubt the customer should consult the designer of the project or the local building control. We would recommend that intumescent coatings are carried out by an approved applicator.
Fire Stopping Shop, disclaim any liability for loss, damage or other expense which may arise from the use of this information, data or products referred to and reserve the right to amend or change any details without notice. This statement does not affect your statuary rights.