Features & Benefits
- Up to 4 hour fire rating (EI240)
- Suitable for PVC, PVC-U, PE, HDPE, MDPE & PP pipes
- Available to suit 50mm, 110mm & 160mm pipes
- Performance unaffected by weathering (Type X Durability)
- Quick & simple installation
- Integrated smoke seal
- Strong lid to carry foot traffic and light access equipment
- No backfilling generally required
- Compact footprint allows for closer positioning of pipes
- Suitable for 150mm or thicker concrete slabs
Product Information
Composition
QuelCast CE Marked Fire Collars are constructed from a robust polypropylene material and contain a high performance intumescent material which reacts under the influence of heat. This will exert pressure on the pipe as it softens, to form a carbonaceous char.
Standards & Approvals
Fire resistance testing to BS EN 1366-3:2009
CE Marked
EI60, EI120, EI180, EI240
Classified to EN 13501-2: 2007 + A1: 2009Product Data Links
Technical Product Documentation
Quelfire - QuelCast Cast In Fire Collar - Product Data Sheet
Quelfire - QuelCast Cast In Fire Collar - Installation Instructions
Quelfire - QuelCast CE Marked Cast In Collars - Installation Instructions for profiled deck
Quelfire - QuelCast Cast in Fire Collar Device CE Marked - Material Safety Data Sheet (COSHH)
Quelfire - QuelCast CE Marked Cast In Fire Collar Device - Certificate of Constancy of Performance
Quelfire - QuelCast CE Marked Cast In Fire Collar Device - Declaration of Performance
Standard Installation Detail Examples
QC-CF150-01 - Plastic Pipes penetrating a rigid floor
QC-CF150-02 - Plastic Pipes penetrating a rigid floor (QuelCast50)
QC-CF150-03 - Undersized Plastic Pipes penetrating a rigid floor
QC-CF150-04 - Cluster of Plastic Pipes penetrating a rigid floor
QC-CF250-06 - Plastic Pipes penetrating a rigid floor (Manifold on top)
QC-CF250-07 - Plastic Pipes penetrating a rigid floor (Manifold to underside)
The above information is based on current test data, health and safety information and application instructions supplied by our suppliers and manufacturers of the products. It is supplied for guidance and to the best of our knowledge is true and accurate. Customers should satisfy themselves to the suitability of the products in its intended use and no guarantee is given or implied as the conditions of actual use are beyond our control. If in doubt the customer should consult the designer of the project or the local building control.