EVERBUILD® FIRESPAN® Intumescent Pads are designed to be used on the inside or outside of electrical socket boxes to maintain fire and smoke barrier where service holes are cut into dry lining and all types of fire rated boarding. High tack adhesion, pliable and mouldable, self-bonding.

    • Dry Lining systems.

    • Around metal or plastic socket boxes.

    • Fire rated partition walls.

     
    Advantages


    • Maintains a fire and smoke barrier around sockets in drylining systems.

    • Excellent acoustic properties.

    • High tack adhesion, pliable and mouldable with excellent self bonding properties.

    • Preformed shape to fit most common socket boxes.


    Intumescing Temperature
     Approx 250 °C Integrity / Insulation 2 Hours* *up to 2 hour fire rating in certain configurations.


    Colour


    Red Stiff Putty


    Product Information

    Chemical Base


    Silicone Rubber Polymer Containing intumescent Fillers


    Shelf Life


    36 months from date of manufacture in original wrapper.


    Storage Conditions


    Store in cool dry conditions away from direct sunlight


    Density


    1.55 - 1.60 g/cm3


    Technical Information

    Resistance to fire


    Test Results: (Tested to EN1366-3) WF Report No. 388629A Issue 2



    Service Ref Aperture dimensions and seal type Service Type
    D 50 mm high by 50 mm wide sealed with NS Putty 150 mm deep Single E (1 x 185 mm²) electric cable
    M 50 mm long by 50 mm wide sealed with NS Putty 60 mm deep, flush at the unexposed face Single E (1 x 185 mm²) electric cable




    Service Ref Aperture dimensions and seal type
    F 2 no. 32 mm deep single gang electric sockets with plastic back-box, 'F1' fitted to the unexposed face and 'F2' fitted to the exposed face
    G 2 no. 32 mm deep single gang electric sockets with plastic back-box, 'F1' fitted to the unexposed face and 'F2' fitted to the exposed face




    Specimen Integrity (minutes) Insulation (minutes)
    Cotton Pad Sustained Flame Gap Gauge
    D 132* 132* 132* 132*
    F1 132* 132* 132* 132*
    F2 132* 132* 132* N/A
    G1 132* 132* 132* 132*
    G2 132* 132* 132* N/A
    Overall Seal 132* 132* 132* 132*
    M 132* 132* 132* 90


    * The test duration. The test was discontinued after a period of 132 minutes.



    Specimens F2 and G2 unable to be given insulation value due to being installed on the exposed face.


    Specimens F1, F2, G1 and G2, as described are not fully in accordance with the requirements of BS EN 1366-3:2009, because they are only partial penetrating, however, if the specimens were to be assessed for integrity and insulation criteria from BS EN 1366-3:2009 the results could be expressed as above.


    Data Sheets

    Product Data Sheet 

    Packaging


    Single Socket - 4mm x 170mm x 170mm


    Double Socket - 4mm x 230mm x 170mm





    The above information is based on current test data, health and safety information and application instructions supplied by our suppliers and manufacturers of the products. It is supplied for guidance and to the best of our knowledge is true and accurate. Customers should satisfy themselves to the suitability of the products in its intended use and no guarantee is given or implied as the conditions of actual use are beyond our control. If in doubt the customer should consult the designer of the project or the local building control. 



    Fire Stopping Shop, disclaim any liability for loss, damage or other expense which may arise from the use of this information, data or products refereed to and reserve the right to amend or change any details without notice. This statement does not affect your statuary rights.

     

    Brand:
    Sika
    weight:
    1000.0
    Product Condition:
    New
    Updating Order Details
    Please do not refresh or navigate away from the page!
    Product Added to your Cart
    x

    -------- OR --------