Putty Pads
EVERBUILD® FIRESPAN® Intumescent Pads are designed to be used on the inside or outside of electrical socket boxes to maintain fire and smoke barrier where service holes are cut into dry lining and all types of fire rated boarding. High tack adhesion, pliable and mouldable, self-bonding.
- Dry Lining systems.
- Around metal or plastic socket boxes.
- Fire rated partition walls.
Advantages
- Maintains a fire and smoke barrier around sockets in drylining systems.
- Excellent acoustic properties.
- High tack adhesion, pliable and mouldable with excellent self bonding properties.
- Preformed shape to fit most common socket boxes.
Intumescing Temperature Approx 250 °C Integrity / Insulation 2 Hours* *up to 2 hour fire rating in certain configurations.
Colour
Red Stiff Putty
Chemical Base
Silicone Rubber Polymer Containing intumescent Fillers
Shelf Life
36 months from date of manufacture in original wrapper.
Storage Conditions
Store in cool dry conditions away from direct sunlight
Density
1.55 - 1.60 g/cm3
Technical Information
Resistance to fire
Test Results: (Tested to EN1366-3) WF Report No. 388629A Issue 2
Service Ref | Aperture dimensions and seal type | Service Type |
---|---|---|
D | 50 mm high by 50 mm wide sealed with NS Putty 150 mm deep | Single E (1 x 185 mm²) electric cable |
M | 50 mm long by 50 mm wide sealed with NS Putty 60 mm deep, flush at the unexposed face | Single E (1 x 185 mm²) electric cable |
Service Ref | Aperture dimensions and seal type |
---|---|
F | 2 no. 32 mm deep single gang electric sockets with plastic back-box, 'F1' fitted to the unexposed face and 'F2' fitted to the exposed face |
G | 2 no. 32 mm deep single gang electric sockets with plastic back-box, 'F1' fitted to the unexposed face and 'F2' fitted to the exposed face |
Specimen | Integrity (minutes) | Insulation (minutes) | ||
---|---|---|---|---|
Cotton Pad | Sustained Flame | Gap Gauge | ||
D | 132* | 132* | 132* | 132* |
F1 | 132* | 132* | 132* | 132* |
F2 | 132* | 132* | 132* | N/A |
G1 | 132* | 132* | 132* | 132* |
G2 | 132* | 132* | 132* | N/A |
Overall Seal | 132* | 132* | 132* | 132* |
M | 132* | 132* | 132* | 90 |
* The test duration. The test was discontinued after a period of 132 minutes.
Specimens F2 and G2 unable to be given insulation value due to being installed on the exposed face.
Specimens F1, F2, G1 and G2, as described are not fully in accordance with the requirements of BS EN 1366-3:2009, because they are only partial penetrating, however, if the specimens were to be assessed for integrity and insulation criteria from BS EN 1366-3:2009 the results could be expressed as above.
Data Sheets
Product Data Sheet
Packaging
Single Socket - 4mm x 170mm x 170mm
Double Socket - 4mm x 230mm x 170mm
The above information is based on current test data, health and safety information and application instructions supplied by our suppliers and manufacturers of the products. It is supplied for guidance and to the best of our knowledge is true and accurate. Customers should satisfy themselves to the suitability of the products in its intended use and no guarantee is given or implied as the conditions of actual use are beyond our control. If in doubt the customer should consult the designer of the project or the local building control.
Fire Stopping Shop, disclaim any liability for loss, damage or other expense which may arise from the use of this information, data or products refereed to and reserve the right to amend or change any details without notice. This statement does not affect your statuary rights.