Lorient CE Marked Intumescent Acoustic Acrylic Sealant Box
Lorient CE Marked Intumescent Acoustic Acrylic Sealant designed to cover the Construction Products Regulation 2011 (CPR) requirement for linear gap seals and penetration seals.When exposed to fire, it expands in volume to fill all cavities; providing a necessary hot smoke seal. Applications
A linear gap seal for gaps in wall and floor constructions as a linear joint seal where the wall and floor constructions abut a penetration seal around metallic pipes & electrical cables to reinstate the fire resistance performance of wall and floor constructions. Seal the perimeter around fire and smoke resistant damper/air transfer grilles in doors, walls, ducts floors and ceilings.
Material
Polymer content increased for improved flexibility - tolerates differential movement in everyday service.
Finishes
White as standard. Other colours available to special order
Product Size
Supplied in individual 310ml cartridges or in boxes of 25 units.
Please call the sales team for smaller or larger quantities - 02476 422200
Storage & Cleaning
Store in cool dry conditions between 5°C - 30°C. Do not allow to freeze. Water based - tools can be cleaned using soap and water.
Performance
Provides effective acoustic containment. Provides up to 240 minutes fire resistance.
Test Evidence
CE Marked Fire: BS EN 1366-3: 2004, BS EN 1366-4: 2006 + BS EN 13501-2: 2016.Acoustic: BS EN 10140-2 :2010. Building Construction: BS EN ISO 8339: 2005. Building Construction: BS EN ISO 9046: 2004 for the types Z1 + Z2 use categories specified in ETAG 026-3. ETA 13/0173, ETA 13/0174, ETAG 026-2 + ETAG 026-3
Product Data Sheet
Data Sheet
The above information is based on current test data, health and safety information and application instructions supplied by our suppliers and manufacturers of the products. It is supplied for guidance and to the best of our knowledge is true and accurate. Customers should satisfy themselves to the suitability of the products in its intended use and no guarantee is given or implied as the conditions of actual use are beyond our control. If in doubt the customer should consult the designer of the project or the local building control.