Pyrogrille Air Transfer Grilles - Rectangular
Rectangular - Pyrogrille air transfer grilles are designed for installation into fire resisting doors or partitions where there is requirement for the passage of free air, such as boiler rooms or IT server rooms. Manufactured by Mann McGowan using high performance intumescent slats spaced 12mm apart, the finished units are 38mm thick. Providing up to two hours fire protection they still allow 60% free air flow in normal use. A range of decorative covers are also available. - Tested in flexible walling and ducting to BS476: Part 20: 1987, offering up to 120 minutes fire integrity
- Tested in timber doors to BS EN1634-1:2014, offering up to 60 minutes fire integrity
- Large range of standard and non-standard sizes available to suit all applications*
- Offers approx. 60% free area
- No moving parts therefore no maintenance required
- Slim design; only 38mm thick
- Can be supplied with a wide range of decorative covers if required
- Simple to install in doors, walls and ducts
- Standard finish is black but other colours are available
*Check with door manufacturer’s fire test evidence for maximum size permissible. Technical
Square and rectangular air transfer/ventillation grilles for fire resisting doors
Description
PYROGRILLE air transfer grilles are manufactured from high performance intumescent slats, spaced 12mm apart. The thickness of the units are 38mm.
Decorative steel cover grilles are available for our square and rectangular units, please consult with our sales office regarding sizes available.
Performance
PYROGRILLES have been subjected to fire resistance tests in accordance with
BS 476 Part 20 : 1987 and assessed to Dutch Norm NEN 6069.
Applications
PYROGRILLE units can be fixed into fire resisting doors or timber stud partitions using a hardwood or steel flange. Alternatively wood screws can be used through the perimeter of the units.
Gaps around the PYROGRILLE unit greater than 3mm should be fire sealed using PYROMAS A intumescent sealant.
Finishes
Standard colour black.
Non standard colours red and bronze.
Maintenance
Since there are no moving parts to go wrong, PYROGRILLES are easily maintained. Units should be cleaned using a damp cloth. Grease can be removed by using neat liquid detergent or methylated spirit. Strong degreasing agents should not be used nor should the units be immersed or saturated with water.
Ordering
When ordering please state, fire resistance required, width, height and colour.
Data Sheet
Product Data Sheet
The above information is based on current test data, health and safety information and application instructions supplied by our suppliers and manufacturers of the products. It is supplied for guidance and to the best of our knowledge is true and accurate. Customers should satisfy themselves to the suitability of the products in its intended use and no guarantee is given or implied as the conditions of actual use are beyond our control. If in doubt the customer should consult the designer of the project or the local building control.
Fire Stopping Shop, disclaim any liability for loss, damage or other expense which may arise from the use of this information, data or products refereed to and reserve the right to amend or change any details without notice. This statement does not affect your statuary rights.